Products
Flam Burner with production above quality standards
today is one of the few manufacturers in Turkey burner.
Flam Burner with production above quality standards
today is one of the few manufacturers in Turkey burner.
THEREE PASSES | ENVIRONMENT FRIENDLY | AUTOMATIC CONTROL SYSTEM
3-pass constructions should be preferred for good combustion, in coal-fire boilers and thus for high efficiency.
Since it allows complete combustion of coal particles, no unburned coal particles spread the environment (soot,) so fuel consumption in vain is prevented. furthermore, since the combustion cell temperature does not rise too much due to the structure of the boiler, the emission values that harm the environment decreases. Operation of burning air ventilator in coal burning is controlled with a thermostat depending on the water temperature in the boilers.
Its installation, operation and maintenance is easy: since ashtray of the boiler is inside its body, there is no need to make a concrete ashtray.
For casting grids resistant against temperature, there is no need for a cooling system. Circulation pump,energy consuption… When the grills are removed, it becomes ready to burn liquid / gas within an hour. Since the combustion chamber temperature does nor rise (since no recersible flame is composed of), harmful NOx formation remains at a minumum level.
It is not appropriate to put a turbulator in the flame tubes in coal-fired boilers. The tubes are clogged in a short time. The need of cleaning the tubes in very short time eventually makes operatör tired, dismantle and blow away the turbulators. İn this case, the thermal capacity and efficiency of the boiler is reduced.
Composed reversing flame formed in the liquid / gas fuel burning increases combustion chamber temperature, it increases harmful NOx formation. This means environmental pollution.
TYPE G-SF / G-HWB-3P-S Capacity and Main Dimensions
TYPE (G-HWB 3P-S) | Steam Capaciy Coal (kg/h) | Steam Capacity Liquid Gas (kg/h) | Without (L) | Width without Armature (E) (mm) | Width without Armature (H) (mm) | Steam Volume (m³) | Water Volume (L) | Stack Diameter (mm) | Flame Roules Resistance (F-Oil-DG) (mmSS) | Approximate Weight 6 Atü (kg/h) | Approximate Weight 10 Atü (kg/h) |
500/100 | 500 | 1000 | 2500 | 2025 | 2125 | 0,75 | 1465 | 400 | 25 | 2650 | 3050 |
750/1500 | 750 | 1500 | 2950 | 2125 | 2225 | 1,14 | 1690 | 400 | 40 | 3560 | 4000 |
1000/2000 | 1000 | 2000 | 3200 | 2300 | 2400 | 1,55 | 1860 | 500 | 50 | 4750 | 5500 |
1500/3000 | 1500 | 3000 | 3700 | 2550 | 2650 | 1,98 | 4165 | 550 | 60 | 6500 | 7500 |
2000/4000 | 2000 | 4000 | 4100 | 2900 | 3000 | 3,17 | 6995 | 600 | 80 | 9150 | 10500 |
2500/5000 | 2500 | 5000 | 4400 | 3050 | 3150 | 3,98 | 7605 | 650 | 90 | 10950 | 12300 |
Dimensions can vary depending on the technological changes.